Smoke and heat spreading through the corridors and the stairs of a building during a fire can limit building occupants’ ability to escape and can limit fire fighters’ ability to rescue them.  Changes in the building’s ventilation or presence of an external wind can increase the energy release of the fire.  This can also increase the spread of fire gases through the building.  In some cases, such as the Cook County Administration Building fire in October 2003, the fire gas flow, into the corridors and the stairway prevented fire fighters from suppressing the fire from inside the structure.  This fire resulted in 6 building occupant fatalities and fire fighter injuries in the stairway.  The Fire Department of New York City has experienced many wind driven fire incidents which have resulted in fire fighter fatalities and injuries.

What tactics or tools are appropriate for use with a wind driven fire and how should the tactics or tools be implemented?  Positive Pressure Ventilation (PPV) is being used by fire departments on smaller structures, such as single family homes, to control the fire flow by introducing pressure from the front door and venting the house through a strategic exit opening.  If done correctly, this tactic can remove significant amounts of heat and smoke from the structure, thus improving the fire fighters’ working environment and improving the chances of survival for the building occupants.  NIST has completed several studies which have a two fold impact: 1) providing guidance on the safe use of PPV and 2) characterizing and validating the modeling of PPV with a computational fluid dynamics (CFD) computer model, so that the model can be used as a training tool for the fire service.

This project extends previous work for ventilation under wind driven conditions.  There are many questions regarding wind driven fires.  For example can these PPV fans be used successfully under wind driven fire conditions in large structures?  Large structures, such as high rise buildings, provide additional challenges to fire fighter and building occupant safety: increased travel distance (exposure time), more complicated egress path, and potentially larger fires.  In 2002 there were 7,300 reported fires in high rise structures.

Other tactics incorporating devices, such as wind control devices (WCD) to control the ventilation conditions or the use of a "high rise" nozzle from the floor below the fire floor have been tried by the fire service under “real fire” conditions with varying levels of success.  Unfortunately, there is no data to understand the capabilities and limitations of these fire fighting approaches.  This effort will address this need for real scale data, to guide the development of appropriate tactical operations for use under wind driven conditions.

Fire Fighting Tactics Under Wind Driven Conditions: Seven-Story Building Experiments

Link to Report TN 1629

In February, NIST, partnering with FDNY and Polytechnic University conducted experiments in order to improve the safety of fire fighters and building occupants by enabling a better understanding of wind driven firefighting tactics, including structural ventilation and suppression. Further objectives include developing technical information that will enhance our understanding of the dynamics of fire phenomena and prediction of fire intensity and growth under wind driven conditions.  The data from this research will help to identify methods of improved standard operating guidelines (SOG) for the fire service to enhance firefighter safety, fire ground operations, and use of equipment.  Results from these experiments will be available by November.  See the Wind Driven Fires section for a compilation video of one of the experiments.

Polytechnic University LogoFDNY Logo     

* This research is funded through a Research and Development Grant from the Assistance to Firefighters Grant Program

GI building image 1GI building image 2

Photographs of the building on Governor's Island that will be used for the experiments.

       WCD Version 2 

Two different types of Wind Control Devices being used to decrease the wind fed to the fire.

 

"High-Rise Nozzles" being implemented and analyzed on their effects for controlling the fire.

    GI building image 2

Photographs from the Governor's Island Wind Driven Fire Experiments.

Videos:

 

                     4-View Video of Experiment 7                                        "High-rise" Nozzle Being Used

 

                      Wind Control Device Deployment                              "Pulsing Fire" with natural wind 

If using Internet Explorer, allow ActiveX to run when prompted. 
If using Mozilla Firefox, you may need to download the Windows Media Plug-in here:  https://addons.mozilla.org/en-US/firefox/browse/type:7.

For description of videos click here.

Downloadable Video Files:

Fire Fighting Tactics Under Wind Driven Conditions: Laboratory Experiments

Link to Report TN 1618

A series of experiments was conducted in our Large Fire Laboratory to examine the impact of wind control curtains and externally applied hose streams on a wind driven fire.  The results from these experiments will allow us to better understand the fire dynamics within a structure and provide guidance as to the important measurements needed in the future experiments in a high-rise on Governor's Island in New York City.

    DHS Logo

* This research is funded through a Research and Development Grant from the Assistance to Firefighters Grant Program

nfpa 1nfpa 2 nfpa 3nfpa 4

Images of the experimental setup in our Large Fire Laboratory

nfpa 5nfpa 6 nfpa 7nfpa 8

Images captured during the 8 experiments conducted.

Videos:

 

Dual View Video of Gas Flow in Laboratory Experiments               8-View Video of Laboratory Experiments

If using Internet Explorer, allow ActiveX to run when prompted. 
If using Mozilla Firefox, you may need to download the Windows Media Plug-in here:  https://addons.mozilla.org/en-US/firefox/browse/type:7.

  • A 4-view video of one of the wind driven fire experiments conducted where the wind control curtain is deployed. The video is 4 times real time. WDF Curtain Deploy (486 MB)
  • An 8-view video of experiment number five conducted at the Large Fire Building at NIST's Gaithersburg Campus which examined the impact of a WCD on a wind driven fire.  The video is 4 times real time. Experiment 5-Oct View (450MB)
  • An 8-view video of experiment number eight conducted at the Large Fire Building at NIST's Gaithersburg Campus which examined the impact of externally applied water, solid stream and fog stream, at 160 gpm.  The video is 4 times real time. Experiment 8- Oct View (419MB)